current location:home pageProduct Center

63518_N77A1 63618_N77A3

Instructions Download>

Model

N77A1/A363518/63618

Regeneration

Time clock type

Mount type

Top mount / side mount

Inlet/outlet

2"M

Drain

1.5"M

Brine line connector

3/4"M

Mounting base

4" -8UN

Riser pipe

1.5" D-GB

Flow rate

18m³/h

Filter tank

24"--42"

Water pressure

0.2-0.6MPa

Water temperature

5-50℃

Water turbidity

20FTU

Relative humidity

≤95%25℃

Power adapter

Input AC100~240V/50~60HZ Output DC24V/1.5A


Product description

N77 Automatic Multiport Softener Valves

Allowing a flow rate of 18m³/h, the N77A automatic multiport softener valve features a planar and corrosion resistant gasket for opening and closing. It is equipped with two valve cores, one controlling the inflow of the water and brine, the other controlling outflow and drainage. The N77A1 is a timer clock type while the N77A3 is meter type.

Product Characteristics

  • Simple structure and reliable sealing

    It adopts hermetic head faces with high degree pottery and corrosion resistance for opening and closing. It combines with Service, Backwash, Brine & Slow Rinse, Brine Refill and Fast Rinse.

  • Two ways for installation

    Use side-mounted connector to change the valve from top-mounted to side-mounted. Screen is moveable.

  • No water pass the valve during regeneration in single tank type

  • Brine refill controlled by electronic ball valve.

    During service, electronic ball valve will control to start the brine refill. In order to short the regeneration cycle time.

  • For filtration system

    Drain outlet is the same size as water outlet. Block the brine line connector change the valve to N77B filter valve.

  • Manual function

    Realize regeneration immediately by pushing “Manual/Return” at any time.

  • Long outage indicator

    If outage overrides 3 days, the time of day indicator “‡” will flash to remind people to reset new time of day. The other set parameters do not need to reset. The process will continue to work after power on.

  • LED dynamic screen display

    The stripe on dynamic screen flash, it indicates the control valve is in service, otherwise, it is in regeneration cycle.

  • Buttons lock

    No operations to buttons on the controller within 1 minute, button lock indicator light on which represent buttons are locked. Before operation press and hold the “Up”and“Down” buttons for 5 seconds to unlock. This function can avoid incorrect operation.

  • It can choose time clock type or meter type by program selection

    Through the switch in control board ((Application refer to Page16) to realize time clock type by day or by hour and meter type. (Attention: after adjust the switch, the valve should be cut off the power then connect again. Meter type valve have one more flow meter and cable then time clock type valve.)